Price | RM1,896.00 |
Product SKU | RM7897C1000/u |
Brand | Honeywell |
Availability | 100 |
Quantity |
|
-
Condition : Brand New
-
Warranty : 1 Year
-
Part Number : RM7897C1000/u
-
Manufacturer : Honeywell
-
Estimated Lead Time: 12 - 18 Weeks
-
RM7897C1000/U
-
BURNR MOD PRMARY; PR/POSTPURGE; 120V; UL
-
On-Off Primary Ctrl with Shutter Drive
-
Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Programmable
-
Post Purge. Requires S7800A1142 Display to program post purge feature.
-
Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
-
Subbase, amplifier and purge card are required for operation.
-
Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and
-
COMBUSTION SYSTEM MANAGER™ software.
-
Five LEDs provide sequence information. Power LED blinks fault code on Safety Shutdown.
-
Interchangeable plug-in flame amplifiers.
-
Local or remote annunciation of operation and fault information.
-
Nonvolatile memory retains history files and sequencing status after power loss.
-
Optional remote reset capability.
-
Optional report generation.
-
Selectable recycle or lockout on loss of airflow or flame.
-
Shutter drive output.
-
Airflow switch check.
-
Delayed main valve.
-
Programmable post purge using S7800A1142 Keyboard Display (not provided).
-
Application:On-Off Primary Control with Pre and Programmable Post purge
-
Dimensions (in.):5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
-
Dimensions (mm):127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase
-
Used With:7800 Series Amplifiers
-
Weight (lb):1 lb 15 oz
-
Weight (kg):0.9 kg
-
Comments:Includes blinking LED fault annunciation feature
-
Frequency:50 Hz; 60 Hz (±10%)
-
Approvals, Underwriters Laboratories Inc.:Component Recognized, File No. MP268; Guide No. MCCZ.
-
Approvals, CSA:Certified, File No. LR95329-3.
-
Voltage:120 Vac (+10, -15%)
-
Shipping and Storage Temperature Range (F):-40 F to +140 F
-
Shipping and Storage Temperature Range (C):-40 C to +60 C
-
Approvals, Federal Communications Commission:FCC Part 15, Class B, Emissions.
-
Flame Establishing Period – Pilot:4 sec or 10 sec
-
Interlocks:Selectable
-
Preignition:Yes
-
PrePurge:Determined by ST7800A Purge Timer Card
-
PostPurge:programmed with S7800A1142 display
-
Required Components:Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in
-
Purge Timer Card.
-
Delayed Main Valve:Yes
-
Pilot Type:selectable
-
Vibration:0.5 G environment
-
Approvals, Control Safety Devices:Acceptable: CSD-1
-
Approvals, Swiss RE:Acceptable
-
Approvals, Factory Mutual:Report No. OX4A5.AF.
-
Shipping Weight: 2 kg
Download PDF File RM7897C1000/U
-
Website : www.nexquickinstrument.com
-
Email : [email protected]
-
Tel : +6019 - 6667611